Current Withstand: 30 A continuously
500 A for 1 sec
Maximum Voltage: 600 V
Contact Resistance: < 2 mΩ
Dielectric Withstand: 5 kV rms for 1 min between adjacent contact pairs and between any contact pair and other metal parts.
2.5 kV rms between open contacts when pin, test probe, or test plug is inserted
IEC 60255-5:2000
Voltage Impulse: 3 positive and 3 negative impulses of 5 kV peak, 1.2/50 µs, 0.5 J between adjacent contact pairs and between all contact pairs and other metal parts
IEC 60255-5:2000
IEEE: Meets or exceeds all requirements of ANSI / IEEE Standard C37.90-2005
Enclosure Protection: IP 20 without cover
IP 50 with dust cover attached
NEMA ANSI / IEC 60529:2004
UL94
Flammability Class:
V-0 (test block, plug and pin plastic housing)
FTL has been classified as electromagnetically benign by the Guide for the EMC Directive 2004/108/EC and is, therefore, excluded from the scope of the EMC Directive.