Current Withstand: 30 A continuously
500 A for 1 sec
Maximum Voltage: 600 V
Contact Resistance: typical max. 1.25mΩ
Dielectric Withstand: 5 kV rms for 1 min between adjacent contact pairs and between any contact pair and other metal parts.
2.5 kV rms between open contacts, when plug is inserted
IEC 60255-5:2000
Voltage Impulse: 3 positive and 3 negative impulses of 5 kV peak, 1.2/50 µs, 0.5 J between adjacent contact pairs and between all contact pairs and other metal parts
IEC 60255-5:2000
IEEE: Meets or exceeds all requirements of ANSI / IEEE Standard C37.90-2005
Enclosure Protection: IP 20 without cover
IP 50 with dust cover attached
NEMA ANSI / IEC 60529:2004
UL94
Flammability Class:
V-0 (test block and test plug plastic housing)
ITS has been classified as electromagnetically benign by the Guide for the EMC Directive 2004/108/EC and is, therefore, excluded from the scope of the EMC Directive.