The Low Power Test Interface System by SECUCONTROL is a safe and efficient solution for testing Low Power Instrument Transformers (LPITs), enabling secure disconnection from the IED and accurate signal measurements. The system includes:
LPS – Low Power Test Switch: A shielded test block that minimizes interference and ensures safe circuit switching.
LPP – Low Power Test Plug: A test plug featuring RJ45 and banana jack connections for secondary injection and direct LPIT signal access.
LPA – Low Power Test Adapter: An adapter that converts conventional test signals to low-power standards, with a wide measurement range.
Designed for quick installation and secondary injection testing without complex disassembly, it meets IEC 61869-11:2019 and ANSI/IEEE C37.90-2005 standards, offering 3.0 kV RMS dielectric withstand and EMI protection.
Ideal for medium- and high-voltage applications, primarily for protection and measurement in GIS.